8 Installation/Operation Manual
2.3 Load Cells
The CB-2 comes pre-wired at the factory. Figure 2-4 shows the loadcell connections on the lower row.
Pin 1
+ SIG
- SIG
+ EXC
- EXC
+ SIG
- SIG
+ EXC
- EXC
Aggregate
Side
Cement Side
Figure 2-4. Terminal Blocks Load Cell Connection (Metered Water)
Table 2-2 lists the load cell connections for a CB-2 automated concrete batching system that contains two load
cells.
Table 2-2. Load Cell Connectors for Units with Two Load Cells (Metered Water)
Bottom Connector - Load Cells
Load Cell Connector Pin Number Signal
Load Cell 1
Aggregates
1 - EXE
2 + EXE
3 - SEN
4 + SEN
5 - SIG
6 + SIG
Load Cell 2
Cement
7 - EXE
8 + EXE
9 - SEN
10 + SEN
11 - SIG
12 + SIG